Electrical Causes of Motor Vibration: How to Separate Them from Mechanics
The motor is humming, there's a line in the spectrum that shouldn't be there, and someone suggests balancing the rotor. Sometimes that's the right call. And sometimes you'll spend a shift and end up with the same level, because the vibration was coming from an uneven air gap or a cracked rotor bar. You can tell one from the other with a single agreed shutdown. Below are the techniques, frequencies, and numbers for doing it right on site.
Where a Motor Gets Vibration That Doesn't Care About Speed
The force with which the stator pulls on the rotor is proportional to the square of the magnetic flux density in the air gap. Square a 50 Hz sine wave and you get a constant term plus a pulsation at 100 Hz. On a 60 Hz supply that's 120 Hz. Every healthy motor has this pulsation; the only question is its level.
In a symmetric machine, the forces around the gap balance each other out, and almost nothing escapes to the outside. Break the symmetry and you're left with an uncompensated force that yanks the rotor to one side a hundred times a second. Three groups of causes break the symmetry: geometry (an uneven gap, a shifted stator, a bent rotor), the magnetic circuit (a loose stator core, a broken rotor bar, shorted turns), and the supply (phase imbalance, a burnt contact, an open phase).
Remember the key property of this vibration: its frequency is set by the mains supply, not the shaft. Load the motor, the speed sags, and the 100 Hz line stays exactly where it was. All the diagnostics that follow are built on this.
This creates two traps people regularly fall into. The first: on a two-pole motor, 2960 rpm gives 1x = 49.3 Hz and 2x = 98.7 Hz, while the supply gives 100 Hz. The difference is 1.3 Hz, and with typical measurement settings these lines merge into one. The second: the 100 Hz force itself can be perfectly normal, and what makes it high is a resonance in the frame or a foot. In that case you'll be hunting for a winding defect where what's actually needed is stiffening the structure.
- The electrical component sits at a frequency that's a multiple of the supply frequency: 100 Hz and 50 Hz on a 50 Hz supply. It doesn't shift along with speed.
- The mechanical component is tied to the shaft: 1x, 2x, vane-pass, bearing frequencies. Change the speed and the whole picture slides along the frequency axis.
- The electrical component usually grows with load, because current and field both grow.
- Imbalance doesn't care about load: the rotor's mass distribution doesn't change because of it.
- The electrical component disappears the instant the contactor opens. The mechanical one lives on as long as the shaft is turning.
A high 100 Hz line on its own isn't a verdict on the windings. It tells you only one thing: the excitation has an electromagnetic origin. The structure's response to that force can be amplified many times over by frame resonance or soft foot, and in that case repairing the motor will get you nowhere. Before hauling the machine off to the electrical shop, tap the frame and check the feet are tight. We have a separate article on resonance and the bump test.
The Coast-Down Test: One Shutdown Instead of Three Hypotheses
This is the cheapest and most convincing diagnostic technique there is. You cut the power and watch what happens to the suspect component in the first few seconds. The electromagnetic force disappears together with the current, within a fraction of a second. The mechanical one decays smoothly, because the shaft is still turning and gradually losing speed.
The key condition: recording has to be continuous through the moment of disconnection. Two separate spectra, before and after, won't settle the question, because you won't see exactly how the line disappeared.
- 01
Get the Shutdown Approved
An unscheduled shutdown is a process risk and an extra start for the motor. Get clearance from operations, agree on who presses the button, and make sure the unit will actually restart afterward. Large machines have a limit on starts per hour, and that limit doesn't go away for your test.
- 02
Set Up the Measurement and Don't Touch It Again
Sensor on the motor's bearing housing, rigidly mounted on a cleaned, flat spot, as close to the bearing as possible. Aim the laser phase sensor (which ties vibration to the shaft's angular position) at the reflective tape mark so you can see speed at the same instant. Don't change the point or the direction for the rest of the test.
- 03
Take the Baseline at the Running Condition
Steady-state speed, working load, a warmed-up machine. A spectrum with enough resolution that 100 Hz and 2x sit as separate lines, plus a time-waveform recording. Record the actual speed with a tachometer — you'll need it to calculate slip.
- 04
Cut the Power and Keep Recording
Start recording a few seconds before the shutdown and don't stop it until the shaft has fully stopped. If the instrument records spectra as a series, set the shortest possible acquisition time, otherwise the moment of disconnection will get smeared out by averaging.
- 05
Review the Recording
The component that cuts off within a fraction of a second after the contactor opens is electrical. The component that creeps down in frequency together with the speed is mechanical. Look at both the spectra and the waveform shape: on the trace, the moment of disconnection is usually visible to the eye as a sharp change in the character of the oscillation.
- 06
If You Can't Shut Down, Change the Load Instead
Take spectra at two or three load conditions at the same or similar speed. Electromagnetic components usually grow with current, while imbalance doesn't care about load. The conclusion is weaker than from a coast-down, but no shutdown is needed and there's no risk.
A variable-frequency drive breaks this test if you don't watch the stop mode. On most drives, a "stop" command means controlled deceleration: the motor is still under current, only the output frequency is falling. In that case the electromagnetic component won't disappear at all — it will just slide down along with the frequency, and you'll get a false "mechanical" conclusion. The test needs a free coast-to-stop mode or a break in the circuit at the drive's output.
Sidebands and Slip Frequency: Calculate Before You Go Looking
An induction motor's rotor always lags behind the stator's rotating field. That difference is slip, and it produces a second set of signs, far more informative than a lone 100 Hz line.
Work through it with real numbers. A four-pole motor on a 50 Hz supply has a synchronous speed of 1500 rpm. The tachometer reads 1480 rpm, so the running frequency f_r = 24.67 Hz, slip s = 20/1500 = 0.0133, slip frequency f_s = s · 50 = 0.67 Hz. Pole-pass frequency F_p = f_s · P = 0.67 · 4 = 2.67 Hz, where P is the number of poles. That's exactly the spacing at which sidebands appear around 1x when the rotor cage has a defect.
In other words, you shouldn't be looking for "something around 24.7 Hz" but for specific lines at 22.0 and 27.3 Hz. The difference between them and 1x is only 2.67 Hz, and this is exactly where typical measurement settings let you down.
Spectrum resolution equals Fmax (the spectrum's upper limit) divided by the number of lines, and the acquisition time for one record equals one divided by that resolution. Fmax of 1000 Hz over 400 lines gives 2.5 Hz per line: the sidebands physically can't separate, and you'll see one broad bump instead. Fmax of 200 Hz over 1600 lines gives 0.125 Hz and requires 8 seconds of acquisition. With settings like that, the sidebands are visible. There's a separate article with more detail on Fmax, line count, and windows.
The second requirement is dynamic range: the measurement's ability to show weak lines next to strong ones. Sidebands from a cracked bar sit 30–50 dB below 1x, so averaging over several records isn't a luxury here, it's the condition for pulling them out of the noise. On a lightly loaded motor, slip is small, the sidebands crowd right up against 1x, and separating them gets even harder. The takeaway is simple: take the spectrum at working load, not at no load.
- Sidebands around 1x spaced at F_p: a broken or cracked rotor bar, a defective end ring, loosened bar fits.
- Sidebands around 100 Hz spaced at F_p: dynamic eccentricity, meaning the gap changes as the rotor turns.
- Sidebands around the rotor slot-passing frequency (the number of bars times f_r) spaced at 100 Hz: the same cage defects, but the sign sits in the kilohertz range, and a velocity measurement over the 10–1000 Hz band simply won't see it.
- Sidebands around the stator slot-passing frequency (the number of slots times f_r) spaced at 100 Hz: a loose stator core, an uneven gap.
- Modulation of 1x itself, which makes the amplitude and phase drift with a period of 1/F_p (0.37 s in our example): the same rotor cage issue or dynamic eccentricity. Balancing under these conditions is pointless — the readings don't repeat.
Sources: ISO 13373-3:2015
Frequency and Sign, Probable Electrical Cause, How to Verify
| Frequency and Sign | Probable Electrical Cause | How to Verify |
|---|---|---|
| 100 Hz on a 50 Hz supply, dominates over 1x, cuts off instantly when power is removed | Uneven air gap, static stator eccentricity, loose stator core | Coast-down test. Gap measurement with a feeler gauge at four points on both sides. Tap the frame and check the feet are tight, to rule out resonance at 100 Hz |
| 100 Hz grows noticeably with load, phase currents differ | Supply imbalance, a weak connection in the terminal box, a burnt starter contact, an open phase | Measure phase voltages and currents and calculate the percentage imbalance. Thermal image of the terminal box, starter, and cable lugs. Retighten the connections |
| Sidebands around 1x spaced at F_p = s · f_line · P | A broken or cracked rotor bar, a defective end ring | Spectrum with 0.1–0.2 Hz resolution at working load. Current spectrum with sidebands at f_line · (1 ± 2s). Thermal image after a loaded run |
| Sidebands around 100 Hz spaced at F_p | Dynamic eccentricity: the gap changes as the rotor turns, a bent shaft, a worn bearing | Gap measurement at several angular positions of the rotor. Shaft runout with a dial indicator. The same coast-down test |
| Rotor slot-passing frequency (bar count × f_r) with 100 Hz sidebands | Loosened or broken bars, a poor connection between the bars and the end ring | Acceleration spectrum with Fmax up to a few kilohertz. Nameplate bar count. From there it goes to the motor repair shop |
| Stator slot-passing frequency (slot count × f_r) with 100 Hz sidebands | Loosened stator-core lamination stack, slot wedges backed out | Inspection and tapping of the core in the shop, checking the wedges, a verification gap measurement |
| 1x is high, but amplitude and phase drift from run to run and change with load | Dynamic eccentricity or a cage defect masquerading as imbalance | Repeat the measurement at two or three loads and check phase repeatability. Coast-down test. Postpone balancing until this is resolved |
| 100 Hz has risen, there's a localized hot spot on the casing, insulation resistance has dropped | A turn-to-turn short in the winding | Electrical tests: insulation resistance, per-phase winding resistance, surge testing. This is a job for the electrician, not the vibration technician |
| Broadband high-frequency noise on a motor driven by a VFD; fluting visible on the bearing raceways at teardown | Bearing currents and electrical discharge machining of the raceways | Shaft voltage measurement. Check for an insulated bearing and a shaft grounding ring. Inspect the raceways at teardown |
| Lines at twice the drive's output frequency and its multiples, a whine in the kilohertz range, the picture changes with the setpoint | The VFD's output voltage and its PWM carrier frequency | Read the drive parameters: output frequency, carrier frequency, braking mode. Check whether the setpoint lands on a resonance |
| 50 or 100 Hz visible in the spectrum even with the machine stopped | Electrical pickup on the measurement chain, not a machine defect | Take a spectrum with the machine stopped. Check the cable, shielding, grounding, and sensor contact. Re-mount the sensor and re-measure |
The table gives you hypotheses, not a diagnosis. You can't choose a repair based on a single 100 Hz line: it has at least four different possible sources, and each one needs its own independent confirmation. The working rule is: coast-down test first, to separate electrical from mechanical, then current and temperature, to narrow the field, and only then teardown.
Six Electrical Defects, One by One
Uneven Air Gap and Static Eccentricity
The stator bore isn't concentric with the rotor's axis of rotation: the stator is offset, the fits are worn, a foot has settled, the frame twisted during installation. The gap on one side is permanently smaller, and the force pulls the rotor that way a hundred times a second. Vibration ends up sharply directional: the level in one radial direction is several times higher than in another. The check is simple: measure the gap with a feeler gauge at four points on both sides of the machine. The spread is usually kept within about 5% of the average; check the documentation for the specific motor for the exact requirement.
Dynamic Eccentricity
Here the rotor isn't concentric with its own axis of rotation: a bent shaft, an off-centre rotor core, a worn bearing that lets the shaft move around in its seat. The gap changes as the rotor turns, and the electromagnetic force gets modulated by the rotation. Sign: sidebands around 100 Hz spaced at F_p, and a modulated, drifting 1x. This is the most deceptive of the electrical defects, because it looks the most like imbalance. It's exactly the one people most often try to fix with weights.
Broken or Cracked Rotor Cage Bar
A cast-aluminium cage cracks from thermal cycling and frequent starts; on a copper one, the usual culprit is a poor connection between a bar and the end ring. Current redistributes across the remaining bars, the field loses symmetry, the torque pulsates. Signs: sidebands around 1x spaced at F_p, rising slip at the same load, a localized hot spot on the rotor, sometimes a pulsating hum. The motor still runs and pulls its load, but starting torque drops, and the crack grows with every start.
Loose Stator Core
The core's laminations lose their clamping pressure, and electromagnetic forces, together with magnetostriction (the ability of iron to change size in a magnetic field), start rocking the core at 100 Hz. It's heard as a hum with a distinct pure tone, and the spectrum shows 100 Hz plus sidebands around the stator slot-passing frequency. It can't be fixed on site: it needs teardown, rewedging, and re-pressing of the core. But it can be confidently suspected on site, saving you from wasting time on balancing.
Turn-to-Turn Short in the Winding
A short across a few turns breaks the field's symmetry: 100 Hz rises, and a localized hot spot appears at the defect. Vibration diagnostics only gives an indirect hint here, and it's more honest to say so directly. It's confirmed by electrical methods: insulation resistance, per-phase winding resistance, surge testing. Don't wait on this — a turn-to-turn short progresses into a phase-to-phase short and a breakdown to ground, at which point the motor no longer gets repaired, it gets replaced.
Supply Imbalance and a Poor Connection
The cheapest item on the list and one of the most common. A loose bolt in the terminal box, a burnt starter contact, mismatched cable cross-sections across phases, a shop-supply imbalance from single-phase loads. A voltage imbalance above 1% is already worth investigating, and the current imbalance ends up several times larger than the voltage imbalance. Checked with a clamp meter and a thermal camera in ten minutes, before any teardown and before any balancing. Start here.
Variable-Frequency Drives: What They Add and What They Break in Diagnostics
A VFD changes the rules of the calculation. For the motor, the supply frequency is no longer 50 Hz but the drive's output frequency, and the electromagnetic pulsation sits at twice that value. If the drive is running at 35 Hz, look for the line at 70 Hz, not at 100 Hz. Calculate slip and pole-pass frequency from the output frequency too, otherwise the sidebands will show up somewhere other than where you expect them.
At the same time, the 100 Hz line can still be present: the DC-link ripple originates from the mains and leaks through into the output voltage. So on a VFD-driven machine you'll see both lines at once, and you shouldn't confuse them.
The PWM carrier frequency (pulse-width modulation, the method the drive uses to synthesize its output voltage) typically lies in the 2 to 16 kHz range. It produces magnetostrictive noise and vibration at the carrier itself, its multiples, and sidebands spaced at the output frequency. A standard velocity measurement over the 10–1000 Hz band doesn't reach that far, and that's normal: you'll hear the carrier as a characteristic whine before you ever see it in the spectrum. It's fixed with drive parameters and an output filter, not with weights on the rotor.
Bearing currents are a separate topic. The drive induces a voltage on the shaft, it discharges through the bearing, spark erosion eats away at the raceways, and fluting appears. Bearing life calculated per ISO 281 is based on load, geometry, and lubrication, and electrical erosion doesn't appear in that model at all. So a bearing that's calculated to last years fails within a season on a VFD-driven machine with no shaft grounding ring. The protection is structural: an insulated bearing, a shaft grounding ring, and a shielded cable with proper grounding.
- Upside: with a VFD you can smoothly change speed and genuinely check for resonance without touching the mechanics.
- Upside: you can bring the machine to exactly the speed you need for a measurement and hold it steady from run to run, and a stable speed is the condition for a repeatable phase measurement.
- Downside: the setpoint range almost certainly includes a speed where running speed or vane-pass frequency hits a resonance. The machine will be calm at 42 Hz and start shaking at 47 Hz, and balancing won't fix that.
- Downside: until you've established the stop mode, the coast-down test proves nothing.
- Downside: without a grounding ring you'll get a bearing defect that looks like ordinary wear but will recur even on a new bearing.
Sources: ISO 281:2007
Current and Temperature: Two Confirmations Without Teardown
Vibration tells you that symmetry has been broken. It doesn't tell you exactly where. Two independent measurements close that gap, and both are done on the running machine.
Current spectrum analysis is, in essence, a cheap way of doing motor current signature diagnostics. Clamp a current probe with an output to an analyzer onto one phase and take a spectrum with the same high resolution as the vibration. With a rotor cage defect, sidebands appear around the supply frequency at f_line · (1 ± 2s). In our example, with a slip of 0.0133, we get 2s · f = 1.33 Hz, so the sidebands sit at 48.67 and 51.33 Hz. The depth of the sidebands relative to the main line is measured in dB. As a rough guide: above 50 dB is considered normal, 40–45 dB is suspicious, and below 40 dB suggests a likely broken bar. Different methodologies use different thresholds, so treat the number as a reason to investigate, not as a verdict.
A thermal image answers different questions. It instantly finds a weak connection in the terminal box and at the cable lugs, shows an uneven heating pattern across the starter's phases, and picks up a localized hot spot on the casing above a turn-to-turn short as well as an overheating bearing housing. The limitation is an honest one: a thermal camera sees the surface, while the rotor cage is hidden inside the machine and cooled by the air flow. Take the thermal image after a loaded run, not a minute after starting, and compare it against past images of the same motor at the same condition.
- Phase voltages and currents at the terminals, with imbalance calculated in percent, not eyeballed.
- Current spectrum with resolution no coarser than 0.1 Hz, with sidebands at f_line · (1 ± 2s) either found or clearly absent.
- Thermal image of the terminal box, starter, and cable lugs.
- Thermal image of the stator casing and both bearing housings after a loaded run.
- Insulation resistance and per-phase winding resistance, if 100 Hz has risen with no obvious geometric cause.
- Actual speed taken from a tachometer, not from the nameplate. The entire slip calculation rests on this number, and an error of 5 rpm shifts the sidebands to where you won't find them.
Balanset-1A measures vibration, speed, and phase, shows the overall level and 1x, builds the spectrum and time waveform across two channels, and keeps an archive of measurements and reports. It doesn't measure current, insulation resistance, or temperature, and it shouldn't claim to. Vibration shows that the cause is electrical; determining exactly which one takes a clamp meter, a thermal camera, and a megohmmeter, working together with an electrician.
Sources: Balanset-1A operation manual
Why Balancing Doesn't Cure Electrical Faults, and How the Attempt Ends
Balancing only works with mass, and only at running speed. The instrument installs a trial weight, watches how the 1x amplitude and phase changed, and derives an influence coefficient — the specific "rotor, supports, foundation" system's response to a known added mass. It then solves the inverse problem and gives you the correction mass and angle.
A 100 Hz line doesn't fit into this scheme at all. It's not at 1x, it's not a multiple of running speed, and its source isn't mass in the first place. No matter how much weight you install, nothing in the air gap changes. The instrument will honestly reduce 1x to the target value and report "within tolerance," while the overall level — in mm/s RMS (root-mean-square) over the 10–1000 Hz band — stays almost the same, because the main contribution was coming from the 100 Hz line. The customer will see the same number as before and reasonably ask what they paid for.
It's worse when 1x really is high, but inflated by dynamic eccentricity or a cage defect. In that case the 1x amplitude and phase drift with a period of 1/F_p — a bit over a third of a second in our example — and drift more slowly along with load and warm-up. The measurement doesn't repeat from run to run. An influence coefficient calculated from a measurement like that is invalid: it describes not the system, but the random instant you happened to press the button.
- The instrument will produce a weight that lands at an effectively arbitrary angle. Vibration is roughly as likely to increase as to decrease.
- You'll add real mechanical imbalance to compensate for an electromagnetic force. That force depends on load, while mass doesn't. At a different operating condition the machine will shake harder than it did before you arrived.
- You'll spend a shift and three or four extra starts on a motor that may already have a cracked cage. Every start is a thermal shock to that same crack.
- You'll lose time. A broken bar and a turn-to-turn short don't stand still — they progress, and the cost of repair grows along with them.
- A report saying "within tolerance" will create a false sense that the machine has been sorted out, and the next person will start the diagnosis from scratch a month later.
There's also an opposite bias people forget about. An electrical defect and imbalance coexist just fine, especially on a motor with a coupling half or a pulley. Finding a 100 Hz line doesn't mean you should throw out the imbalance hypothesis: first eliminate the electrical cause, then take a fresh measurement, and only then decide whether balancing is needed. Choose the residual-imbalance standard by G class from the applicable part of ISO 21940, and assess the machine's condition by overall vibration and the zones in ISO 20816, checking the applicable part and edition for your machine.
Sources: ISO 21940-11:2016 · ISO 20816-1:2016
Who to Hand the Task To, and What We Bring When We Come Out
Balanset instruments are designed and manufactured by engineers who use them to do field balancing themselves. That's where this article's practical framework comes from: first prove the vibration comes from imbalance, and only then install weights. Balanset-1A gives you everything you need for that proof: two channels on the bearing housings, a laser phase sensor using a reflective tape mark, 1x amplitude and phase, speed, spectrum and time waveform, an archive of measurements, and a report where the before-and-after numbers land.
If 1x is confirmed, you remove it with the same instrument: single- or two-plane balancing using the influence coefficient method, fixed positions instead of a protractor, drilled-hole calculation, recalculating weights for other planes, and saved influence coefficients for a quick trim balance at the next service. There's a Balanset-1A OEM version without the case, for building into machine tools and test stands. If 1x isn't confirmed, you've saved a shift and a few extra starts, and that's a result too.
AXILINE comes out to the site with this equipment: measurement, breaking vibration down into its components, finding the cause, in-situ balancing in the machine's own bearings, a report with the numbers. If the picture points to electrical causes, we'll say so directly and hand the task to an electrician, instead of installing weights on the rotor. We also provide consulting support on the instrument itself: helping with measurement settings and spectrum interpretation.
- To mechanics: the 100 Hz line is amplified by frame resonance, there's a soft or settled foot, the bedplate has twisted, a worn bearing has let the gap drift. This is adjustment and tightening, often on site and the same day.
- To the site electrician: phase current and voltage imbalance, a weak connection in the terminal box or starter, questions about VFD parameters, a missing shaft grounding ring. The cheapest group of causes, and the sensible one to start with.
- To the motor repair shop: a broken cage bar, a turn-to-turn short, a loose stator core, static eccentricity from worn fits. This is teardown, not adjustment, and gets resolved by shutting down and replacing or repairing the motor.
- To the vibration technician: the signs contradict each other, a shutdown can't be arranged, a high-resolution spectrum and a properly recorded coast-down are needed, or after the electrical cause has been eliminated a high 1x remains and needs to be removed.
Sources: Balanset-1A manufacturer specification
Frequently asked questions
The machine can't be shut down. How can you still tell whether the vibration is electrical?
Work with load and frequency. Take spectra at two or three load conditions at similar speeds: electromagnetic components usually grow along with current, while imbalance doesn't care about load. Next, check whether the suspect line sits exactly at 100 Hz (on a 50 Hz supply) or actually at a value that's a multiple of running speed — that needs a spectrum resolution of around 0.1–0.2 Hz. And take a current spectrum with a clamp meter; the sidebands at f_line · (1 ± 2s) are visible there without a shutdown. The conclusion will be weaker than from a coast-down, but usually good enough to avoid making a wasted trip to balance.
On a two-pole motor, 2x and 100 Hz nearly coincide. How do you separate them?
At 2960 rpm, 2x = 98.7 Hz, while the supply gives 100 Hz — a difference of 1.3 Hz. For the lines to separate, you need a resolution no coarser than 0.2–0.3 Hz: for example, Fmax of 200 Hz over 1600 lines gives 0.125 Hz with 8 seconds of acquisition per record. On top of that, keep the speed stable, otherwise the mechanical line will smear and merge back with the supply line. If the resolution isn't enough or the speed drifts, there's still the coast-down test: it separates these two lines unambiguously, because one cuts off instantly and the other creeps downward.
Can a motor with a high 100 Hz line be balanced?
The 100 Hz line itself doesn't get in the way of balancing — it simply doesn't respond to it. What does get in the way is different: if the same electromagnetic cause is modulating 1x, the running-speed component's amplitude and phase stop repeating, and the influence coefficient comes out invalid. The sequence is: make sure 1x is stable in amplitude and phase from run to run and across different loads. If it's stable, and 1x accounts for a substantial part of the level, balance it. If it's drifting, postpone balancing and sort out the electrical issue.
The motor runs from a VFD. At what frequency should you look for the electrical component?
At twice the drive's output frequency, not at 100 Hz. If the output is 35 Hz, look for 70 Hz. Calculate slip and pole-pass frequency from the output frequency as well. At the same time, 100 Hz can still appear in the spectrum because of DC-link ripple, so both lines can be present at once. The PWM carrier sits in the 2–16 kHz range and doesn't show up in a standard velocity measurement up to 1000 Hz — you'll usually hear it as a whine instead. And check the stop mode: under controlled deceleration the motor stays under current, and the coast-down test won't show you anything.
Sidebands around 1x have already turned up. Is it still necessary to measure current?
Yes, if the decision at hand is whether to tear the motor down. Sidebands around 1x spaced at the pole-pass frequency give you a strong hypothesis, but not the only one: dynamic eccentricity and modulation from nearby equipment can draw a similar picture, and the spacing is easy to get wrong with an imprecisely measured speed. A current spectrum checks the same hypothesis through a different physical channel, and the sidebands at f_line · (1 ± 2s) read more reliably there. Plus a thermal image: it finds a weak connection, which also raises both vibration and phase imbalance, and it only takes ten minutes.
We balanced it, 1x dropped, but the overall level barely changed. What got missed?
Most likely, 1x wasn't the main contributor to the overall level to begin with. Look at the spectrum again and figure out which line is carrying the level: 100 Hz points to electrical causes, a pronounced 2x with axial vibration points to misalignment, a comb of harmonics with a drifting phase points to looseness, high-frequency peaks that aren't multiples of running speed point to a bearing. That's exactly how it should work: balancing only reduces the running-speed component, and that's its only job. This comparison of overall vibration against 1x is worth doing before balancing, not after — it changes the conversation with the customer.
Related content
Hydraulic Causes of Pump Vibration: Cavitation, Vane-Pass Frequency, and Operating Point
Hydraulics produces vibration that doesn't live at running speed, and weights have no effect on it. Cavitation produces a "gravel" crackle and a broadband rise across roughly 1 to 10 kHz, recirculation at low flow produces unstable subsynchronous components (vibration at frequencies below running speed), and vanes passing the diffuser or volute tongue produce a peak at the vane-pass frequency f_v = z · n / 60, where z is the number of vanes and n is the speed in rpm. Telling all this apart from imbalance is straightforward: hydraulics responds to valve position, flow rate, and suction head, while imbalance responds to nothing except speed. First restore the operating point and the NPSH margin (the cavitation pressure margin at the suction), then re-measure, and only then decide whether balancing is needed.
How to balance an electric motor rotor: the on-site procedure
An electric motor's rotor is balanced fully assembled, right in its own bearing housings: two sensors on the bearings, a laser phase sensor on the reflective tape on the shaft, a trial weight in an accessible plane — usually on the cooling fan or the half-coupling. Before that, separate the electrical cause from the mechanical one: cut power at operating speed and watch whether the vibration disappears instantly (electrical) or fades along with the speed (unbalance). If the rotor is longer than half its diameter and runs at 1500–3000 rpm, balance in two planes. After rewinding, the rotor is balanced separately on a machine, but final trimming is almost always done on site, in the assembled machine.
On-site balancing of electric motor and generator rotors
Yes, we balance electric motor and generator rotors on site, in their own supports, at operating speed. Three conditions apply. First: the vibration has to be dominated by the 1x running-speed component — vibration at the rotor's rotational frequency, the main sign of imbalance — rather than by line frequency and its second harmonic. Second: at least one correction plane needs to be accessible, meaning a spot where a weight can be fitted: usually the cooling fan, the coupling, a balancing ring, or the rotor face. Third: the fits, bearings, and fasteners have to be sound, because weights don't cure play. If the rotor is coming off anyway (rewinding, bearing replacement, restoring the mounting surfaces), it makes more sense to balance it on a machine in the workshop, and we'll say so plainly rather than fit weights through a hatch.
Describe your equipment and the problem
We'll answer your questions, clarify the details, and let you know what's needed for an estimate and a visit.